Commissioning Systems Selection Matrix

The following table is used to determine which Systems and Items are to be commissioned for the various building types GSA delivers. Column 1 is the Commissioned System. Column 2 is the Item Included within that system. Columns 3 through 7 are the five major Building Types GSA provides our customers. If a dot appears in the box under the building type, then the item in column 2 must be commissioned for that building type.

Commissioned
System
Items
Included
Federal
Office
Building
(FOB)
Border
Station
Courthouse Laboratory Data
Center
Building Envelope Walls (vapor barriers, weeps, building joints)

Windows

Doors

Roofing

Special arch. elements (dome, cornice, etc.)

Envelope (blast, hurricane, thermal, infiltration)

Plumbing System Cleaning/flushing water systems

Cleaning/flushing storm drainage systems

Cleaning/flushing sanitary sewage systems

Cleaning/flushing lab drainage systems

Thermometers & gauges

Sump pumps and ejectors

Trap primers

Backflow preventers/relief valves

Water heaters, water coolers

Domestic water booster pumps

Vibration isolation

Lab waste neutralization

High purity water system

Special gas manifolds

Vacuum air system

Compressed air systems

Emergency shower / eyewashes

Deionized water system

Fuel oil / gas systems

Irrigation systems

Water filtration (General Use)

Showers/Lavs/Toilets

Heating, Ventilating and Air Conditioning (HVAC) Thermometers & gauges

Vibration isolation

Steam condensate systems

Hot water heating systems

Computer room air conditioning units

Chemical water treatment systems

Liquid chillers

Cooling towers

Condenser water system

Chilled water system

Air terminal unit system/VAV units

Humidifiers

Duct silencers

Fire and smoke/fire dampers

Variable speed drives

Air distribution systems

Exhaust air systems

Laboratory fume hoods

Back to Top

Commissioning Systems Selection Matrix (continued)
Commissioned
System
Items Included Federal
Office
Building
(FOB)
Border
Station
Courthouse Laboratory Data
Center
Automatic Temperature Control System (ATC) Component FPT and calibration

Control air supply

Air terminal units, non lab

Air terminal, lab supply/fume exhaust

Sequence control, AHU 100% OSA

Sequence control, EAHU

Sequence control, AHU, H&V

Sequence control, exhaust air fans

Sequence control, differential bypass valve

Sequence control, air terminal units, CV

Sequence control, air terminal units, VAV/CV

Sequence control, air terminal units, VAV

Sequence control heat exchanger

Sequence control, variable speed pumps

Sequence control, cabinet unit heaters

Sequence control, condenser water system

Sequence control, steam humidifiers

Sequence control, water heaters

Sequence control, heating coils/radiant panels

Sequence control, labs with VAV fume hoods

Sequence control, condenser water filters

Sequence control, steam generator

Graphic display

Trend logs

Status review screens, checks & alarming

Network communication

Electrical Systems Electrical primary voltage system

Service switchgear

Emergency power system

Generators

Lighting controls (scheduled / occupancy sensors)

Daylight dimming controls

Switchboards

Distribution panel boards

Transformers

Motor control centers

Power monitoring & metering

Transient voltage surge suppressors

Variable speed drives

Grounding & ground fault systems

Overcurrent protective devices

Low voltage busway

Thermographic Survey

Electronic calendaring or directory

White sound system

Data & communication system

Paging system

Local devices (switches and outlets)

Back to Top

Commissioning Systems Selection Matrix (continued)
Commissioned
System
Items
Included
Federal
Office
Building
(FOB)
Border
Station
Courthouse Laboratory Data
Center
Life Safety Systems Fire suppression / protection systems

Egress pressurization / Atrium smoke purge

Fire alarm

Fire suppression / protection systems

Emergency lighting systems

General egress (panic hardware, etc.)

Elevator recall

Security Access Control

Alarm monitoring

Surveillance

Specialties Elevators

Escalators

Cold rooms

Kitchen/food service

Audio visual systems

Automatic doors

Dark rooms

Oil / water separators

Detention Mains